CHECK VALVE
Check Valves are available in numerous types, styles and shapes. Generally a Valve manufacturer builds only of check valve. VALWORTH builds three types. Therefore, we offer the consulting engineer open, objective and unbiased information about a broad rang of check valves and their proper selection and application. The purpose of this brochure is to collect and condense the many desirable features of the most common type checks into a single source.
Although check valves look different, they each perform the same basic function which is flow through one direction and no flow (check) return. Check valves are commonly installed on the discharge side of the pump . The most important role of check valve is to act as the automatic shut off valve, when the pumps stops to prevent draining of the system which the pump fills. However, each check valve has different shut-off characteristics. This brochure reviews these characteristics to help you select the best check valve for your Project.
APPLICATIONS
PUMPS
STEAM
AIR
GAS
WATER
OIL
VACUUM LINES
CHEMICAL
OTHER
APPLICABLE STANDARDS
  Valworth Wafer type check Valves design to conform To the following standard where applicable.
API 6D I ANSI B 16. 10 Design and Face-to-Face dimensions.
API 594 Wafer type check valve
API 598 Valve Inspection & Testing.
DIN 3230 Testing Standards.
DIN EN 558 – 2 Design Standard.
ANSI B16.5 Flanges End connections.
TEST PRESSURE FOR VALVES
Class min. Test Pressure Psi(g)
Shell Hydro Seat Hydro Air Seat
150# 425 300 80
300# 1100 800 80
400# 1450 1060 80
600# 2175 1600 80
MINIMUM DURATION OF TEST PRESSURE
SIZE DURATION
SHELL SECONDS
12” & SMALLER 60 60
14” & LARGER 120 120
MAXIMUM ALLOWABLE LEAKAGE AS PER API 594
  The maximum permissible leakage rate for Metal seated valves shall be 0.18 cubic inches(3 cubic centimeters) per minute per inch of nominal valve size. The leakage rate for resilient seated valves shall be zero.